Technical Information & Details for the Cabur CL5R Linear Power Supply
- Output Power: up to 120 W (at 24 V DC / 5 A)
- Output Voltage Range: 1.2 – 24 V DC adjustable (1.5 – 24 V DC per model description)
- Output Current: 0.8 – 5 A continuous (rating-dependent)
- AC Input Voltage Range: 12 – 24 V AC nominal (10 – 26 V AC, 47 – 63 Hz)
- Current Consumption: 6 A (at 24 V AC)
- Output Ripple: < 50 mVpp (at 24 V AC)
- Hold-Up Time: > 20 ms
- Internal Protection Fuse: T 10 A (external AC protection: C-10 A or T 10 A)
- Operating Temperature Range: −20 °C to +45 °C
- Mounting & Clearance: vertical on DIN rail (IEC 60715 / TH35-7.5), 20 mm spacing from adjacent components
- Protections: short circuit, overload, input overvoltage
- Overvoltage Category / Pollution Degree: OVC II / Pollution Degree 2
- Isolation: input/output not isolated; input/ground & output/ground 0.5 kV AC / 60 s
- Protection Degree & Housing: IP00, aluminum housing, 2.5 mm² screw terminals
- Approximate Weight: 350 g
- Safety & EMC Standards: EN 62368-1, EN 61000-3-2, EN 61000-3-3, EN 61000-4-2 to -6 and -11, EN 61000-6-2, EN 61000-6-4
- Status Indication: no status LED
- Manufacturer Warranty: per Cabur standard terms
Information on the Cabur CL5R
Designed as a stabilized linear power supply fed from a 12–24 V AC secondary transformer, the Cabur CL5R provides adjustable DC output up to 24 V DC alongside low output ripple under 50 mVpp at 24 V AC. Linear regulation up to 5 A continuous current and a hold-up time above 20 ms make it well suited for noise-sensitive DC loads inside control panels.
Installation calls for vertical mounting on a TH35-7.5 DIN rail with at least 20 mm clearance from adjacent components while operating across a −20 °C to +45 °C temperature range. Its IP00 aluminum housing with 2.5 mm² screw terminals and roughly 350 g weight combines sturdy heat-sinking construction with a compact panel footprint.
Compliance with EN 62368-1 and EMC standards EN 61000-6-2 and EN 61000-6-4 supports deployment in industrial automation and control enclosures. Designers should note that input and output are not isolated from each other, whereas both input and output are isolated to ground at 0.5 kV AC for 60 seconds.
Short-circuit, overload, and input overvoltage protections together with an internal T 10 A fuse help safeguard continuous panel operation. Paired with recommended external C-10 A or T 10 A protection on the 47–63 Hz AC line, the unit integrates cleanly into low-voltage AC distribution setups.