Technical Information & Details for the MEAN WELL TDR-240-24 Power Supply
- Output Power: 240 W
- Output Voltage: 24 V DC
- Output Current: 10 A
- Input Voltage Range: Three-Phase 340 – 550 V AC (Dual-phase operation possible) / 480 – 780 V DC, 47 – 63 Hz
- Efficiency: 92%
- Ripple & Noise: 150 mVp-p
- Inrush Current: Cold start 50 A
- No-load Power Consumption: Not specified (Built-in passive PFC function)
- Operating Temperature: −30 °C to +70 °C
- Cooling: Fanless free air convection
- Protections: Short circuit, Overload (Constant current limiting), Over voltage, Over temperature
- Overvoltage Category: OVC III
- Isolation Voltage: 4.87 KV AC between Input and Output
- Dimensions (H x W x D): 125.2 mm x 63 mm x 113.5 mm
- Weight: 1000 g
- Safety & EMC Certificates: UL61010, BS EN/EN61558, EAC TP TC 004, CE, AS/NZS61558
- LED Indicator: DC OK status indicator with relay contact
- Manufacturer Warranty: 3 Years
Information about the MEAN WELL TDR-240-24
The MEAN WELL TDR-240-24 is a high-performance three-phase industrial DIN rail power supply engineered to deliver 240W of reliable power in a remarkably slim 63mm housing. This space-saving design is critical for modern control cabinets where rail density is a priority. One of its most versatile features is the wide-range three-phase input of 340 to 550 V AC, which also supports dual-phase operation, providing essential redundancy and flexibility for various global electrical grids. With an efficiency rating of 92% and a rugged metal casing, the unit minimizes heat dissipation and operates effectively under free air convection across a temperature range of -30 °C to +70 °C, ensuring longevity even in harsh environments.
Equipped with advanced functional features, the TDR-240-24 includes a built-in passive PFC function to comply with harmonic current regulations and a DC OK relay contact for seamless integration into automated monitoring systems. The unit utilizes a constant current limiting circuit for overload protection, making it an ideal choice for powering inductive or capacitive loads found in semiconductor fabrication, factory automation, and electromechanical apparatus. Furthermore, its compliance with UL61010 and Overvoltage Category III (OVC III) standards ensures superior protection against line surges, making it a highly competitive and secure solution for mission-critical industrial applications and high-altitude operations up to 5000 meters.