Technical Information & Details for the LUETZE LOCC-Box-EC I4-C3 Load Monitoring

  • Product Family: LOCC-Box-EC Eco
  • Nominal Current: 4 A (fixed current range)
  • Trip Characteristic: Slow-2 (C4)
  • Nominal Voltage / Working Range: DC 12/24 V (DC 10–30 V)
  • Switch-on Capacity: up to 10,000 µF
  • Voltage Drop: < 170 mV at full load
  • Status Indication: LED green (operation), LED red (fault in load circuit)
  • Signaling Output: Transistor, collector with pull-up resistor
  • Operating Temperature Range: −25 °C to +50 °C
  • Storage Temperature Range: −40 °C to +85 °C
  • Enclosure Material & Fire Protection: PA 6.6 (UL 94 V-0, NFF 12, F2)
  • Protection Class: IP20
  • Dimensions (W x H x D): 8.1 mm x 114.5 mm x 116.0 mm
  • Weight: approx. 0.105 kg
  • Mounting & Termination: Snap-on for TS35 DIN rail (EN 60715), spring clamp terminal
  • Certifications: cULus (E135145)
  • Standards: EN 60950-1, EN 61131-1,2, EN 61000, EN 60947-4-1, EN 55022

Information on the LUETZE LOCC-Box-EC I4-C3

Safeguarding critical industrial DC distribution lines requires high-precision hardware such as the electronic load monitoring module LUETZE LOCC-Box-EC I4-C3 for fault isolation and uptime protection. Engineered for 12V and 24V control environments, the device delivers a strict, fixed nominal current of 4 A to prevent thermal overloads. To handle high startup demands without unwanted interruptions, its predefined slow-2 (C4) trip characteristic safely manages capacitive surge loads up to 10,000 µF. Built for demanding panel environments, the module maintains reliable, long-term operation across an extended operating temperature range of −25 °C to +50 °C.

Optimizing panel space utilization is made effortless by an ultra-slim enclosure profile measuring only 8.1 mm in width, maximizing DIN rail packing density. Fast, secure installation is accomplished through reliable spring-clamp terminals and an internal copper busbar system that minimizes wiring complexity. Rapid electronic switching via MOSFET elements, coupled with built-in reverse polarity protection, ensures immediate fault response times. Local visual diagnostics are instantly provided via dual-color LED indicators, while an integrated transistor status output links seamlessly with higher-level PLCs.

Maintenance efficiency is significantly accelerated through flexible configuration options for individual or centralized group fault reporting, reducing troubleshooting time. Constructed from flame-retardant PA 6.6 housing material, the unit complies with strict industrial fire safety standards including UL 94 V-0 and railway specification NFF 12, F2. Worldwide commercial deployment is fully enabled by mandatory international certifications such as cULus (E135145), ensuring smooth integration into export machinery. This intelligent device serves as a superior electronic upgrade over conventional thermal-magnetic circuit breakers.

Control system designers and panel builders value the seamless blend of space-saving dimensions, effortless TS35 DIN rail snap-on mounting, and precise channel protection. Full compliance with rigorous international electromagnetic compatibility and safety standards—such as EN 60950-1—highlights LUETZE's dedication to industrial excellence. Whether deployed in factory automation, process systems, or specialized machinery, this advanced monitoring solution secures critical assets and maximizes operational reliability.


Verfügbare Downloads
Download LOCC-Box-EC Datenblatt
Eigenschaften für "LOCC-Box-EC I4-C3"
Approval: UL
Height: 114,5
Length: 8,1
Protection Rating: IP20
Rated current: 10
Voltage: 12 VDC, 24 VDC
Weight: 0,12kg
Width: 116